Air Shower:
Specifications :-
4 Persons | 1400 | 1800 | 2000 | 2300 | 2000 | 2140 | 3020 |
3 Persons | 800 | 1800 | 2000 | 1700 | 2000 | 2140 | 3020 |
2 Persons | 800 | 800 | 2000 | 1700 | 1000 | 2140 | 1500 |
Air shower for No. of IPersons | W1 | D1 | H1 | W | D | H | Power Consumption (In Watts) |
Inner Dimensions | Overall Dimensions |
Specification of Air Showers - Through Entry/Exit :-
Specifications | MODEL | |||
RAS-A-TE | RAS-8-TE | RAS-C-TE | RAS-M-TE | |
Diemensions Of Work Area - WIDTH -HEIGHT -DEPTH |
800 MM 2,000 MM 1,000 MM |
800 MM 2,000 MM 2,000 MM |
1,400 MM 2,000 MM 2,000 MM |
800 MM 2,000 MM 1,600 MM |
Net Weight In KGS (Approx.) | 350 KGS | 700 KGS | 750 KGS | 600 KGS |
Number of persons washed at a Time | 1 - 2 | 2 - 4 | 4 - 6 | 2 - 3 |
Number of Nozzles | 16 | 32 | 32 | 32 |
Power consumption in Watts (Approx) | 1120 | 2240 | 2240 | 2240 |
Power Supply | 415 V.AC, 3 Phase, 50 HZ, 4 Wire | |||
Air Jet Velocity - M/Sec. | Side Nozzles -30 +(-) 3 Top Nozzles - 25 +(-) 2 |
|||
Equivalent Velocity Pressure MM Of WG | Side Nozzles - 55 +(-) 0.55 Top Nozzles -38 +(-) 0.25 |
|||
Sound Level At 100 Cms from Equip. When Blower is On & Doors Closed | 65 dba When Ambient Sound Level Is Not Greater Than 55 dba | |||
Main Body Doors Flooring Pre Filters Hepa Filters |
MS CRCA, 1.2 MM Thick with Stoving Enamel Ivory Paint A) Aluminium Doors with Glass MS with 2 MM Thick PVC Sheet HDPE, Washable, 90% to 10 Micron Class-100, Efficiency - 99.97% Down to 0.3 Micron |
|||
Operation |
|
|||
Door Interlocking |
|
|||
Maintenance Excess | From Inside the Work Area |
Air Shower:
Features :-
Company Profile: